Input SchnittstellenTyp Bool 0.0 false True False False False False Interface type (0= Bus, 1= PFC) MaschinenTypBlock Bool 0.1 false True False False False False Machine type BloFill block machine Anlagenregelung Bool 0.2 false True False False False False Plant regulation available TCIP_Einl_Vorh Bool 0.3 false True False False False False T-CIP infeed available TCIP_Ausl_Vorh Bool 0.4 false True False False False False T-CIP outfeed available BTR_KHS_S_00_0 Bool 0.5 false True False False False False fr. transport: Reserved for DP/DP coupler BTR_KHS_S_00_1 Bool 0.6 false True False False False False fr. transport: UPS power failure BTR_KHS_S_00_2 Bool 0.7 false True False False False False fr. transport: UPS bridging time end BTR_KHS_S_00_3 Bool 1.0 false True False False False False fr. transport: BTR_KHS_S_00_4 Bool 1.1 false True False False False False fr. transport: Confirm infeed conveyor runs for T-CIP infeed BTR_KHS_S_00_5 Bool 1.2 false True False False False False fr. transport: Confirm outfeed conveyor runs for T-CIP outfeed BTR_KHS_S_00_6 Bool 1.3 false True False False False False fr. transport: BTR_KHS_S_00_7 Bool 1.4 false True False False False False fr. transport: Lifebit BTR_KHS_S_01_0 Bool 1.5 false True False False False False fr. transport: BTR_KHS_S_01_1 Bool 1.6 false True False False False False fr. transport: Infeed max BTR_KHS_S_01_2 Bool 1.7 false True False False False False fr. transport: Infeed min BTR_KHS_S_01_3 Bool 2.0 false True False False False False fr. transport: Infeed ready BTR_KHS_S_01_4 Bool 2.1 false True False False False False fr. transport: Outfeed max BTR_KHS_S_01_5 Bool 2.2 false True False False False False fr. transport: Outfeed min BTR_KHS_S_01_6 Bool 2.3 false True False False False False fr. transport: Outfeed ready (fault stop with operator restart) BTR_KHS_S_01_7 Bool 2.4 false True False False False False fr. transport: Outfeed ready (warning stop with autom. restart) BTR_KHS_S_02_0 Bool 2.5 false True False False False False fr. transport: Emptying active [container exactly filling] BTR_KHS_S_02_1 Bool 2.6 false True False False False False fr. transport: Close stop for emptying [container exactly filling] BTR_KHS_S_02_2 Bool 2.7 false True False False False False fr. transport: Close stop for closure change [container exactly filling] BTR_KHS_S_02_3 Bool 3.0 false True False False False False fr. transport: BTR_KHS_S_02_4 Bool 3.1 false True False False False False fr. transport: BTR_KHS_S_02_5 Bool 3.2 false True False False False False fr. transport: BTR_KHS_S_02_6 Bool 3.3 false True False False False False fr. transport: BTR_KHS_S_02_7 Bool 3.4 false True False False False False fr. transport: BTR_KHS_S_03_0 Bool 3.5 false True False False False False fr. transport: BTR_KHS_S_03_1 Bool 3.6 false True False False False False fr. transport: BTR_KHS_S_03_2 Bool 3.7 false True False False False False fr. transport: BTR_KHS_S_03_3 Bool 4.0 false True False False False False fr. transport: BTR_KHS_S_03_4 Bool 4.1 false True False False False False fr. transport: BTR_KHS_S_03_5 Bool 4.2 false True False False False False fr. transport: BTR_KHS_S_03_6 Bool 4.3 false True False False False False fr. transport: BTR_KHS_S_03_7 Bool 4.4 false True False False False False fr. transport: BTR_KHS_S_08 DInt 6.0 0 True False False False False fr. transport: Set output (Bus= container/hour, PFC= 0..27648) KHS_Lifebit Bool 10.0 false True False False False False Filler lifebit Fkt_Zutransport Bool 10.1 false True False False False False Fct.enable: Infeed on Fkt_Abtransport Bool 10.2 false True False False False False Fct.enable: Outfeed on Fkt_Anlagenregelung Bool 10.3 false True False False False False Fct.enable: Plant regulation on AutoAnlaufAktiv Bool 10.4 false True False False False False Automatic machine start-up active FuellungAktiv Bool 10.5 false True False False False False Filling operating mode active LeerfahrenAktiv Bool 10.6 false True False False False False Machine emptying active LeereBehaelter Bool 10.7 false True False False False False Empty containers AntriebFreigabe Bool 11.0 false True False False False False Enabling main drive Maschinentakt Bool 11.1 false True False False False False 1:1 machine clock MaschineDreht Bool 11.2 false True False False False False Machine running MaschineSteht Bool 11.3 false True False False False False Machine standstill SperreGeoeffnet Bool 11.4 false True False False False False Stop opened BehaelterEingelaufen Bool 11.5 false True False False False False Containers in the machine BehaelterAusgelaufen Bool 11.6 false True False False False False Container run out BehaelterEinAuslaufAnz Int 12.0 0 True False False False False Number of containers in the machine [PC4.0] BehaelterEinlaufAnz DInt 14.0 0 True False False False False Number of containers run in with automatic reset [PC4.0] BehaelterAuslaufAnz DInt 18.0 0 True False False False False Number of containers run out with automatic reset [PC4.0] VorstopperAktiv Bool 22.0 false True False False False False Stop open/closed with pre-stop is active VorstopperVollziehen Bool 22.1 false True False False False False Section behind pre-stop gets full VorstopperBandstopp Bool 22.2 false True False False False False Request infeed conveyor stop for machine emptying (pre-stop) TCIP_EinlaufEin Bool 22.3 false True False False False False Request infeed conveyor on for T-CIP infeed TCIP_AuslaufEin Bool 22.4 false True False False False False Request outfeed conveyor on for T-CIP outfeed Aussenreinigung Bool 22.5 false True False False False False External cleaning active Auto_Behaelt_Eingel DWord 24.0 16#0 True False False False False Number of containers run in with operator reset [container exactly filling] Auto_Getraenkemenge1 Real 28.0 0.0 True False False False False Amount of beverage to be filled in liter (mixer + filler) [c.e.f.] Auto_Getraenkemenge2 Real 32.0 0.0 True False False False False Amount of beverage to be filled in liter (syrup room) [c.e.f.] Auto_Behaelt_Volumen Int 36.0 0 True False False False False Container volume in 0.1ml [container exactly filling] T_EinlaufMax Timer 38.0 0 True False False False False Timer off-delay infeed max T_AuslaufMin Timer 40.0 0 True False False False False Timer off-delay outfeed min T_EinlaufMaxZeit S5Time 42.0 S5T#0ms True False False False False Delay time off-delay infeed max T_AuslaufMinZeit S5Time 44.0 S5T#0ms True False False False False Delay time off-delay outfeed min Ist_Leistung_x100 Int 46.0 0 True False False False False Actual output (x100 container/hour) Max_Leistung_x100 Int 48.0 0 True False False False False Max output (x100 container/hour) Soll_Leistung_x100 Int 50.0 0 True False False False False Set output (x100 container/hour) Output KHS_BTR_S_00_0 Bool 52.0 false True False False False False to transport: Reserved for DP/DP coupler KHS_BTR_S_00_1 Bool 52.1 false True False False False False to transport: Request infeed conveyor lubrication on KHS_BTR_S_00_2 Bool 52.2 false True False False False False to transport: Request outfeed conveyor lubrication on KHS_BTR_S_00_3 Bool 52.3 false True False False False False to transport: Request infeed conveyor stop for machine emptying (pre-stop) KHS_BTR_S_00_4 Bool 52.4 false True False False False False to transport: Request infeed conveyor on for T-CIP infeed KHS_BTR_S_00_5 Bool 52.5 false True False False False False to transport: Request outfeed conveyor on for T-CIP outfeed KHS_BTR_S_00_6 Bool 52.6 false True False False False False to transport: Container run out 50:50 [PC4.0] KHS_BTR_S_00_7 Bool 52.7 false True False False False False to transport: Lifebit KHS_BTR_S_01_0 Bool 53.0 false True False False False False to transport: Plant regulation on KHS_BTR_S_01_1 Bool 53.1 false True False False False False to transport: Emptying active KHS_BTR_S_01_2 Bool 53.2 false True False False False False to transport: Infeed on KHS_BTR_S_01_3 Bool 53.3 false True False False False False to transport: Outfeed on KHS_BTR_S_01_4 Bool 53.4 false True False False False False to transport: Machine running KHS_BTR_S_01_5 Bool 53.5 false True False False False False to transport: Container in machine KHS_BTR_S_01_6 Bool 53.6 false True False False False False to transport: Machine clock KHS_BTR_S_01_7 Bool 53.7 false True False False False False to transport: Enable infeed KHS_BTR_S_02_0 Bool 54.0 false True False False False False to transport: KHS_BTR_S_02_1 Bool 54.1 false True False False False False to transport: KHS_BTR_S_02_2 Bool 54.2 false True False False False False to transport: KHS_BTR_S_02_3 Bool 54.3 false True False False False False to transport: KHS_BTR_S_02_4 Bool 54.4 false True False False False False to transport: KHS_BTR_S_02_5 Bool 54.5 false True False False False False to transport: KHS_BTR_S_02_6 Bool 54.6 false True False False False False to transport: KHS_BTR_S_02_7 Bool 54.7 false True False False False False to transport: KHS_BTR_S_03_0 Bool 55.0 false True False False False False to transport: KHS_BTR_S_03_1 Bool 55.1 false True False False False False to transport: KHS_BTR_S_03_2 Bool 55.2 false True False False False False to transport: KHS_BTR_S_03_3 Bool 55.3 false True False False False False to transport: KHS_BTR_S_03_4 Bool 55.4 false True False False False False to transport: KHS_BTR_S_03_5 Bool 55.5 false True False False False False to transport: KHS_BTR_S_03_6 Bool 55.6 false True False False False False to transport: KHS_BTR_S_03_7 Bool 55.7 false True False False False False to transport: KHS_BTR_S_08 DInt 56.0 0 True False False False False to transport: Actual output (Bus= container/hour, PFC= 0..27648) KHS_BTR_S_12 DInt 60.0 0 True False False False False to transport: Max output (Bus= container/hour, PFC= 0..27648) KHS_BTR_S_16 DInt 64.0 0 True False False False False to transport: Set output (Bus= container/hour, PFC= 0..27648) KHS_BTR_S_32 DInt 68.0 0 True False False False False to transport: Number of containers in the machine [PC4.0] KHS_BTR_S_36 DInt 72.0 0 True False False False False to transport: Number of containers run in with automatic reset [PC4.0] KHS_BTR_S_40 DInt 76.0 0 True False False False False to transport: Number of containers run out with automatic reset [PC4.0] KHS_BTR_S_44 DInt 80.0 0 True False False False False to transport: Number of containers run in with operator reset [c.e.f.] KHS_BTR_S_48 Real 84.0 0.0 True False False False False to tr.: Amount of bev. to be filled in l. (mix + fill) [c.e.f.] KHS_BTR_S_52 Real 88.0 0.0 True False False False False to transport: Container volume in liter [container exactly filling] KHS_BTR_S_56 Real 92.0 0.0 True False False False False to tr.: Amount of bev. to be filled in l. (syrup room) [c.e.f.] BTR_Lifebit Bool 96.0 false True False False False False Transport lifebit EXT_USV_Fehler Bool 96.1 false True False False False False External UPS power failure EXT_USV_Ende Bool 96.2 false True False False False False External UPS bridging time end Max_EinlaufOk Bool 96.3 false True False False False False Infeed conveyor ready for max output Max_AuslaufOk Bool 96.4 false True False False False False Outfeed conveyor ready for max output Auto_Leerfahren Bool 96.5 false True False False False False to automation: Emptying active [container exactly filling] Soll_Regelung_x100 Int 98.0 0 True False False False False Set output plant regulation (x100 container/hour) StatusEingaenge1 Int 100.0 0 True False False False False Status interface signals to the visualization page 1 StatusAusgaenge1 Int 102.0 0 True False False False False Status interface signals to the visualization page 1 StatusEingaenge2 Int 104.0 0 True False False False False Status interface signals to the visualization page 2 StatusAusgaenge2 Int 106.0 0 True False False False False Status interface signals to the visualization page 2 InOut TCIP_EinlaufOk Bool 108.0 false True False False False False Confirm infeed conveyor runs for T-CIP infeed TCIP_AuslaufOk Bool 108.1 false True False False False False Confirm outfeed conveyor runs for T-CIP outfeed F_Mangel_Lst Bool 108.2 false True False False False False Notice: Half output container lack F_Mangel_Sperre Bool 108.3 false True False False False False Notice: Container lack F_Mangel_Sperre_LP Bool 108.4 false True False False False False Notice: Container lack F_Mangel_Sperre_PD Bool 108.5 false True False False False False Notice: Container lack F_Stau_Lst Bool 108.6 false True False False False False Notice: Half output container back-up F_Stau_Sperre Bool 108.7 false True False False False False Notice: Container back-up F_Stau_Sperre_TP Bool 109.0 false True False False False False Notice: Container back-up F_Stau_Sperre_PD Bool 109.1 false True False False False False Notice: Container back-up F_StoerungZutransport Bool 109.2 false True False False False False Fault: Fault infeed conveyor F_StoerungAbtransport Bool 109.3 false True False False False False Fault: Fault outfeed conveyor (fault stop with operator restart) F_WarnungAbtransport Bool 109.4 false True False False False False Fault: Fault outfeed conveyor (warning stop with autom. restart) F_Beh_genaues_Abfuell Bool 109.5 false True False False False False Notice: Container exactly filling active F_Ver_genaues_Abfuell Bool 109.6 false True False False False False Notice: Closure exactly filling active modeManagerOutput "LibFF_ModeManagerOutput_UDT" 110.0 True False False False False progManagerOutput "LibFF_ProgramManagerOutput_UDT" 116.0 True False False False False stateManagerOutput "LibKHS_StateManagerOutput_UDT" 122.0 True False False False False Static ProduktionAktiv Bool 128.0 false True False False False False Production active M_Mangel_Sperre_LP Bool 128.1 false True False False False False Auxil. flag container lack M_Stau_Sperre_TP Bool 128.2 false True False False False False Auxil. flag container back-up